Address:
1328 Puerto Drive Apollo Beach FL 33572
Total Vents:
20
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
10
Low / Intake Vents:
(Within Lower 1/3 of Attic)
10
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
3,883
Code Required Method:
1/300 (EXCEPTION)
Calculation:
3,883 ÷ 300 = 12.94 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
12.94
Calculation:
12.94 x 144 = 1,863.36 sq. in. of Code Required Ventilation
Square Inches Provided:
(20 x 97.50) = 1,950 sq. in.
clay Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?