Total Vents:
112
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
56
Low / Intake Vents:
(Within Lower 1/3 of Attic)
56
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
9,900
Code Required Method:
1/150 (EXCEPTION)
Calculation:
9,900 ÷ 150 = 66 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
66
Calculation:
66 x 144 = 9,504 sq. in. of Code Required Ventilation
Square Inches Provided:
(112 x 86.25) = 9,660 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.