Total Vents:
26
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
13
Low / Intake Vents:
(Within Lower 1/3 of Attic)
13
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,900
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,900 ÷ 150 = 12.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
12.67
Calculation:
12.67 x 144 = 1,824.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(26 x 72) = 1,872 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.