Total Vents:
164
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
82
Low / Intake Vents:
(Within Lower 1/3 of Attic)
82
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
14,600
Code Required Method:
1/150 (EXCEPTION)
Calculation:
14,600 ÷ 150 = 97.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
97.33
Calculation:
97.33 x 144 = 14,015.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(164 x 86.25) = 14,145 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.
Vent Solutions