Total Vents:
184
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
92
Low / Intake Vents:
(Within Lower 1/3 of Attic)
92
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
16,500
Code Required Method:
1/150 (EXCEPTION)
Calculation:
16,500 ÷ 150 = 110 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
110
Calculation:
110 x 144 = 15,840 sq. in. of Code Required Ventilation
Square Inches Provided:
(184 x 86.25) = 15,870 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.