Address:
5555 S. JUNIPER HILLS DR, GOLD CANYON, AZ
Total Vents:
8
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
4
Low / Intake Vents:
(Within Lower 1/3 of Attic)
4
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
777
Code Required Method:
1/150 (EXCEPTION)
Calculation:
777 ÷ 150 = 5.18 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
5.18
Calculation:
5.18 x 144 = 745.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(8 x 98.75) = 790 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions