Address:
7166 LA JOLLA SCENIC SOUTH DRIVE, LA JOLLA, CA, 92037
Total Vents:
28
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
14
Low / Intake Vents:
(Within Lower 1/3 of Attic)
14
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
2,050
Code Required Method:
1/150 (EXCEPTION)
Calculation:
2,050 ÷ 150 = 13.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
13.67
Calculation:
13.67 x 144 = 1,968.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(28 x 72) = 2,016 sq. in.
Wood shake
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions