Address:
7166 LA JOLLA SCENIC SOUTH DRIVE, LA JOLLA, CA, 92037
Total Vents:
10
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
5
Low / Intake Vents:
(Within Lower 1/3 of Attic)
5
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
740
Code Required Method:
1/150 (EXCEPTION)
Calculation:
740 ÷ 150 = 4.93 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
4.93
Calculation:
4.93 x 144 = 709.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(10 x 72) = 720 sq. in.
Wood shake
Low Profile (Tapered)
NET FREE VENTILATION AREA
1/4" Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions
Questions?