Address:
9331 Pennywood Road Santee, CA 92071
Total Vents:
10
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
5
Low / Intake Vents:
(Within Lower 1/3 of Attic)
5
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,750
Code Required Method:
1/300 (EXCEPTION)
Calculation:
1,750 ÷ 300 = 5.83 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
5.83
Calculation:
5.83 x 144 = 839.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(10 x 97.50) = 975 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.