Total Vents:
2
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
1
Low / Intake Vents:
(Within Lower 1/3 of Attic)
1
Metal Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
233
Code Required Method:
1/300 (EXCEPTION)
Calculation:
233 ÷ 300 = 0.78 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
0.78
Calculation:
0.78 x 144 = 112.32 sq. in. of Code Required Ventilation
Square Inches Provided:
(2 x 70.20) = 140.40 sq. in.
Standing Seam metal
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 70.20 sq. in.