Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5245'
Required Method:
1/300
Calculation:
5245 ÷ 300 = 17.48 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
17.48
Calculation:
17.48 x 144 = 2517.12 sq. in of Code Required Ventilation
Square Inches Provided:
(26 x 98.75) = 2567.5 sq. in
Square Inches Needed:
17.48 x 144 = 2517.12 sq. in
Where do I install vents graphic
Vent Placement
High / Exhaust Vents Needed:
13
Low / Intake Vents Needed:
13
Total Vents Needed:
26
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Wire Mesh 98.75 sq. in
Figures based on independent evaluation reports.