Total Vents:
42
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
21
Low / Intake Vents:
(Within Lower 1/3 of Attic)
21
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
4,200
Code Required Method:
1/150 (EXCEPTION)
Calculation:
4,200 ÷ 150 = 28 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
28
Calculation:
28 x 144 = 4,032 sq. in. of Code Required Ventilation
Square Inches Provided:
(42 x 98.75) = 4,147.50 sq. in.
clay Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.