Total Vents:
40
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
20
Low / Intake Vents:
(Within Lower 1/3 of Attic)
20
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
7,100
Code Required Method:
1/300 (EXCEPTION)
Calculation:
7,100 ÷ 300 = 23.67 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
23.67
Calculation:
23.67 x 144 = 3,408.48 sq. in. of Code Required Ventilation
Square Inches Provided:
(40 x 86.25) = 3,450 sq. in.
clay Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.