25748 Hawthorne Pl, Stevenson Ranch, CA 91381 (Roof Planes L, M, O)
Total Vents:
12
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
6
Low / Intake Vents:
(Within Lower 1/3 of Attic)
6
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
1,040
Code Required Method:
1/150 (EXCEPTION)
Calculation:
1,040 ÷ 150 = 6.93 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
6.93
Calculation:
6.93 x 144 = 997.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(12 x 97.50) = 1,170 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.