Address:
433 Marketplace San Ramon, CA 94583
Total Vents:
148
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
74
Low / Intake Vents:
(Within Lower 1/3 of Attic)
74
Comp Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
22,000
Code Required Method:
1/300 (EXCEPTION)
Calculation:
22,000 ÷ 300 = 73.33 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
73.33
Calculation:
73.33 x 144 = 10,559.52 sq. in. of Code Required Ventilation
Square Inches Provided:
(148 x 72) = 10,656 sq. in.
Composition shingle
Low Profile (Tapered)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 72 sq. in.
Figures based on independent evaluation reports.
Vent Solutions