Address:
10976 ALTO COURT OJAI, CA. 93023
Total Vents:
6
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
3
Low / Intake Vents:
(Within Lower 1/3 of Attic)
3
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
450
Code Required Method:
1/150 (EXCEPTION)
Calculation:
450 ÷ 150 = 3 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
3
Calculation:
3 x 144 = 432 sq. in. of Code Required Ventilation
Square Inches Provided:
(6 x 88.87) = 533.22 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 88.87 sq. in.
Figures based on independent evaluation reports.