Address:
10553 Cory Lake Drive Tampa, FL 33647
Total Vents:
30
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
15
Low / Intake Vents:
(Within Lower 1/3 of Attic)
15
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
5,980
Code Required Method:
1/300 (EXCEPTION)
Calculation:
5,980 ÷ 300 = 19.93 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
19.93
Calculation:
19.93 x 144 = 2,869.92 sq. in. of Code Required Ventilation
Square Inches Provided:
(30 x 97.50) = 2,925 sq. in.
concrete Tile Vents
High Profile (S)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 97.50 sq. in.
Figures based on independent evaluation reports.
Vent Solutions