Address:
116 Via Capri Palm Beach Gardens, FL
Total Vents:
60
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
30
Low / Intake Vents:
(Within Lower 1/3 of Attic)
30
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
12,040
Code Required Method:
1/300 (EXCEPTION)
Calculation:
12,040 ÷ 300 = 40.13 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
40.13
Calculation:
40.13 x 144 = 5,778.72 sq. in. of Code Required Ventilation
Square Inches Provided:
(60 x 98.75) = 5,925 sq. in.
concrete Tile Vents
Low Profile (Flat)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 98.75 sq. in.
Figures based on independent evaluation reports.
Vent Solutions