Address:
3195 Firenze Place, Highlands Ranch, CO 80126
Total Vents:
60
Where do I install vents graphic
Vent Placement Recommendations
High / Exhaust Vents Needed:
(Within 3' of Ridge Assembly)
30
Low / Intake Vents:
(Within Lower 1/3 of Attic)
30
Tile Roof Drawing
Total Square Feet of Attic Space to be Ventilated
Total Square Feet of Attic Space to be Ventilated:
10,434
Code Required Method:
1/300 (EXCEPTION)
Calculation:
10,434 ÷ 300 = 34.78 sq. ft. of Code Required Ventilation
Convert square feet of code-required ventilation to square inches
Square Feet of Code Required Ventilation:
34.78
Calculation:
34.78 x 144 = 5,008.32 sq. in. of Code Required Ventilation
Square Inches Provided:
(60 x 86.25) = 5,175 sq. in.
concrete Tile Vents
Medium Profile (M)
NET FREE VENTILATION AREA
Noncombustible, Corrosion-Resistant Wire Mesh 86.25 sq. in.
Figures based on independent evaluation reports.